Single Phase Motor flc Table
HP
120v flc
fuse
dual element
breaker
THW
208v flc
fuse
dual element
breaker
THW
240v flc
fuse
dual element
breaker
THW
HP
.5
9.8
30
20
25
14
5.4
20
15
15
14
4.9
15
15
15
14
.5
1
16
50
30
40
14
8.8
30
20
25
14
8
25
15
20
14
1
1.5
20
60
35
50
12
11
35
20
30
14
10
30
20
25
14
1.5
2
24
80
45
60
10
13.2
40
25
35
14
12
40
25
30
14
2
2.5
29
90
60
80
8
15.95
50
30
40
14
14.5
45
30
40
14
2.5
3
34
110
60
90
8
18.7
60
35
50
12
17
60
30
45
12
3
3.5
39.5
125
70
100
8
21.72
70
40
60
10
19.75
60
35
50
12
3.5
4
45
150
80
125
4
24.75
80
45
70
10
22.5
70
40
60
10
4
4.5
50.5
175
90
150
4
27.27
90
50
70
10
25.25
80
45
70
10
4.5
5
56
175
100
150
4
30.8
100
60
80
8
28
90
50
70
10
5
5.5
60.8
200
110
175
4
33.44
110
60
90
8
30.4
100
60
80
8
5.5
6
65.6
200
125
175
4
36.08
110
70
100
8
32.8
100
60
90
8
6
6.5
70.4
225
125
200
3
38.72
125
70
100
8
35.2
110
70
90
8
6.5
7
75.2
250
150
200
3
41.36
125
80
110
6
37.6
125
70
100
8
7
7.5
80
300
150
200
3
44
150
80
110
6
40
125
70
100
8
7.5
8
84
300
150
225
2
46.2
150
90
125
6
42
150
80
110
6
8
8.5
88
300
175
225
2
48.4
150
90
125
6
44
150
80
110
6
8.5
9
92
300
175
250
2
50.6
175
90
150
6
46
150
90
125
6
9
9.5
96
300
175
250
1
52.8
175
100
150
4
48
150
90
125
6
9.5
10
100
300
175
250
1
55
175
100
150
4
50
150
90
125
6
10

flc from 430.248 - All Single Phase - Next larger standard size when calculated value is not in 240.6
fuse non-time delay 300% - dual element 175% - breaker inverse time 250%
THW copper @ 125% of flc then 310.16 from 75 degree C column